UNIVERSAL DIGITAL GENERATOR CONTROLLER JUST LIKE DEEP SEA
HGM6300 Series generator controller integrating digital, intelligent and network techniques is used for automatic control system of diesel generator. It can carry out functions including automatic start/stop, data measure and alarming. The controller uses LCD display, optional Chinese and English display interface with operation easy and reliable.
HGM6300 Series generator controller uses micro-processing technique which can carry out precision measure, constant value adjustment, timing and threshold setting and etc. of multi-parameters. It can be widely used in all types of generator automatic control system for compact structure, advanced circuits, simple connections and high reliability.
2. Performance and characteristics
HGM6300 controller has two types:
HGM6310: ASM (Automatic Start Module)
HGM6320: AMF (Automatic Mains Failure Module)
Using microprocessor as a core, graphics LCD with big screen and backlight, display between Chinese and English, key touch for operation.
Precision measure and display of
generator apparent power (kVA)
generator cumulate electric energy (kWh)
Configurable single phase 2 wires or three phase 3 wires or three phase 4 wires AC system input;
Control protection: Automatic start/stop, load transfer and alarming of generator;
Parameters setting: Allow user to modify setting and store them inside internal FLASH memory, the parameters can not be lost even with power down.
Three channel analog inputs, may joint with Resistive-type temperature/ pressure/ fuel level sensors, Several temperature and pressure sensors can be used directly (ie. VDO, DATCON, CUMMINS), also may select user defined sensor via entering 16 point curves;
Functions including RTC(real time clock) and hours count;
Display of generator cumulated electric energy;
Security password-protected programming levels.
Several crank success conditions are optional;
Built-in speed/frequency detecting units can accurately judge the states such as crank success and over speed;
99 historical records can be stored circularly and inquiring of the records can be made on site;
Power supply range is wide, accommodating to different starting battery voltage environments;
All parameters use digital modulation, abandoning analog modulation using conventional electronic potentiometer, reliability and stability are increased;
Built-in watch dog can never be dead halt, ensuring smooth program execution;
Modular configuration design, inserted type connection terminals, flush type installation, compact structure, easy installation.
DC8. 0V to 35. 0V, Continuous Power Supply
50Hz - 60 Hz at rated engine speed
10,000 Hz (max) at rated engine speed.
1-3 16 Amp DC at supply voltage 4 6A 250VAC
16A 250VAC free voltage contact
Charge Fail / Excitation Range