Fire Detection Devices ThermoflexFixed Temperature Heat Detector Model #CF 135-2
This listing is for a new in the package Thermoflex Fixed Temperature Heat detector Model #CF 135-2. The other numbers on the boxes are 4098-9429 and Part #677-268.
The Model CF 135 is a Fixed Temperature Only detector. The fixed temperature portion consists of a spring-loaded plunger retained by a fusible alloy that releases when the ceiling temperature reaches 57 degrees Celsius, (135 degrees F). When released, the plunger strikes a normally open set of contacts and holds them closed. Spacing on an uninterrupted ceiling is 40' (12.5 m).